Flame Test Equipment

single-flame source test

 

 

Ignitability test (EN ISO 11925-2)

 

 

 

 

 

Description

 

Ignitability test, also called single-flame source test.Test apparatus corresponds to standard EN ISO 11925-2. Test results of the building structure can be classified according to standard 13501-1.

The dimensions of the test specimens shall be (250 ) mm long by (90 ) mm wide.
450-tilted burner is advanced horizontally until the flame (length 20 mm) reaches the pre-set contact point with the test specimen. Tests may need to be conducted to either surface exposure or edge exposure, or both. The flame application time is 15 or 30 seconds as required by sponsor.

During the test following is recorded: whether ignition occurs; whether the flame tip reaches 150 mm above the flame application point, and the time at which this occurs; whether ignition of the filter paper occurs; observations of physical behavior of the test specimen.

 

二、Specifications

   This apparatus made up of two parts: burning chamber and control device.

Burning chamber:

  Dimension: 700 * 400 * 810mm

  Burner: diameter 0.17mm burner with regulator

  Burner angle: 45°

  Vent: diameter 150mm on the top

  Material: stainless steel

  Observing window: two big viewing windows on the front and right side

Control device:

  Power supply: 220VAC

  Timer: two separate timers record the burning time and lasting time

  Fan: on or off

  Lighting: on or off

 

三、features

* Stainless steel test cabinet, satisfy the requirements of the newest standards;

* Two big observing windows to let operator view test process easy;

* Bottom of cabinet is cross-shaped stainless steel reseau to keep well venting;

* Specimen holder can move up & down and left & right;

* Equipped with two stainless steel specimen holders to satisfy different test standards.